IS 3b impulse control

de
RWZ 1-4b

Description

This SHEV control uses a 24 VDC pulse output to control electromagnets/solenoid valves (e.g. RTC-E) or pneumatic valves with electrical components (EA / EZ). The IS 3 pulse control allows the setup of a smoke and heat exhaust group and has two detection lines. It delivers a total output current of 4 A.

Please note the approved batteries for use in our smoke and heat exhaust control panels and controllers.

Specifications

  • Mains voltage supply 230 VAC
  • Output current 4 A (24 VDC / 96 W)
  • SHE groups 1
  • Detection lines 2
  • Accumulators 2 x 2 Ah / 12 V
  • Backup time 72 h in case of power failure
  • Environmental class 1/III -5 °C to +40 °C
  • Housing protection class IP30
  • Dimensions 330 mm x 330 mm x 110 mm

Variants

  • Solenoid control IS 3-4b 4 A / 24 VDC, 2x 2 Ah / 12 V

  • Option PK potential-free contacts (PK) for forwarding alarm and/or fault messages.
  • Modul MA convenient connection of a normally closed or normally open contact.

Accreditations

ISO 21927-9:2012, EN 12101-10:2005, VdS 2581 und VdS 2593